Fairbanks X SERIES PR 5410 Process Indicator User Manual
Page 49
Section 3: Installing the Instrument and Plug-In Cards
10/08 49
51207 Revision 1
3.4.12 PR 1721/37 EtherNet/IP Schnittstelle
The EtherNet/IP interface is a plug-in card for installation in Slot 4, see chapter 3.4.1. The card is
fitted with a standard RJ-45 socket for Ethernet connection and contains a powerful TCP/IP and
EtherNet/IP connecting circuitry with transfer rates of 10 and 100Mbits/s.
Internal connection:
34-pin connector on flat cable for
Slot-4
External connection:
RJ-45 connecting socket in holding
plate
Transfer rate:
10Mbit/sec and 100Mbit/sec
Autodetection (10/100,
HalfDX/FullDX)
Connection mode:
Network
Protocol:
EtherNet/IP
Transport:
TCP/IP oder UDP/IP
Cable:
Twisted pairs, screened
e.g. patch cable CAT5
Autolink (straight oder crossover)
Cable impedance:
150 Ohm
Cable length to HUB: Max. 115 m
Certificates:
EtherNet/IP Specification
ODVA File No. 10286
Test Date: 06.09.2005
Vendor ID 90
See also: www.odva.org
Tested according to: CE, UL & cUL
Potential isolation:
Yes
Dimensions (LxWxH): 87 x 55 x 15mm
Weight:
125 g
The EtherNet/IP card is supported from PR 5410 Firmware Release 1.30 onwards. The IP-Address
and the Subnet-Mask are set at Fieldbus parameter FP 96 und 97 (see chapter 4.7.7 and Error!
Reference source not found.).
Take care, that switches 1 - 8 are set to (OFF)
LED 1
LED 2
LED 3
LED 4
Off
No connection (HW) No power
No power o.
No IP Address
On green
Connection (HW)
Controlled by a
scanner
Online,
connection
established
On red
Major unrecoverable
fault
IP Address double,
fatal error
Flasching green
Not configured o.
scanner in idle state
Online, no connection
established
packet is received or
transmitted
Flashing red
Minor recoverable
fault
Connection timeout
Alternat.
red/green
Self test in progress Self test in progress
Watchdog LED
Flashing 1Hz
green
Modul initialized and running without problems