Section 3: Installing the Instrument and Plug-In Cards

10/08 27

51207 Revision 1

3.4.4 PR 5510/04 Serial I/O


The plug-in card has two channels (1x RS-232 and 1x RS-422/485), which can be used
simultaneously and to a great extent independently. The RS-422/485 interface is electrically
isolated. Up to 2 PR 5510/04 cards (Slot 1 and 2) can be plugged in. The relevant interface

parameters can be configured under

-[Serial ports parameter]; the DIL switch S101 must be set

for RS-422/485 additionally.

Internal connection:

34-contact socket terminal strip

Number of channels: 1x RS-232, 1x RS-422/485
Type:

RS-232 full duplex
RS-422/485 full duplex (4-wire)
*
RS-485 half duplex (2-wire)
*

Transfer rate:

300 to 19k2 bit/s

RS-232C (V24)
signals:

Output: TXD, RTS, DTR
Input: RXD, CTS, DCD, RI

RS-422/485 signals: TxA, RxA, TxB, RxB
Electrical isolation:

RS-232: no, RS-422 / 485: yes

Cable length:

Max. 15m with RS-232
Max. 1000 m with RS-422 / 485

Cable type:

Shielded twisted pair
(e.g., LifYCY 3x2x0,20),
1 conductor pair for GND.

External connection:

2 D-Sub 9-contact female
connectors

Accessories
(delivered with the
unit):

2 D-Sub 9-pin mating plugs
(male)
incl. shielded housing

Dimensions:
(LxWxH):

86 x 52 x 15 mm

Weight:

33 g



PR 5510/04 RS-232

The RS-232 interface is independent of the S101 switch settings.
It can be used only for point-to-point connection.

PR 5510/04 is provided as an equivalent to the [Builtin RS-232] interface in the RS-232 channel with
additional signals: DCD, DTR, RI.

The built-in and PR 5510/04 interfaces comply with the standard pin allocation; i.e., they are
equivalent in the following connecting diagrams. Thus only the RS-232 connections for the built-in