Section 4: Commissioning

10/08 87

51207 Revision 1

[Remote display]

Select the serial interface to which the remote display is connected and then select [Param] to
define the [Baudrate] and the remote display type [Mode] connected.

Setup/Serial ports/Builtin RS232

Assigned to

Remote display

Protocol

Remote display

Baudrate

9600 bd Select [Baudrate] with

and

Bits

7

set the baud rate with

Parity

even

Stopbits

1

Mode

single transmitter


The available baud rates are 300, 600, 1200, 2400, 4800 or 9600. The parameters (displayed in
light-gray) cannot be changed.
If only 1 instrument is connected to a PR1627/8 (normal case), [Mode] must be set to [single
transmitter].
Foe a PR1577 remote display [PR 1577 mode] has to be set.
If more than 1 instrument are connected to 1 remote display, [Mode] must be set to [multiple
transmitters].
At [Device Id] the own instrument address (A, B, C ...) has to be entered, at [Next Device Id] the
address of the subsequent instrument has to be entered.

[JBUS/MOD-Bus]

Setup/Serial ports/Builtin RS232

Assigned to

JBUS/MOD-Bus

Protocol

JBUS/MOD-Bus

Baudrate

9600 bd Select [Baudrate] with

and

Bits

8

set the baud rate with

Parity

even None, odd or even

Stopbits

1

Slave

1 Select an address; 1 to 255

Press

to return to the [Serial ports parameter] setup menu. When you close this menu, the

following messages are displayed if at least one setting was changed:

Save settings

Start JBUS/MOD-Bus


The JBUS/MOD bus protocol is described in Chapter 4.9.