Section 4: Commissioning
10/08 88
51207 Revision 1
4.7.3 SMA Protocol
Select an RS-485 interface under
-[Serial ports parameter].
Setup/Serial ports
Printer
- none -
Remote display
Slot1 RS232
JBUS/MOD-Bus
Slot2 RS485
SMA
Slot1 RS485
Param
Only the baud rate is adjustable; the other parameters are fixed.
Setup/Serial ports/Slot1 RS485
Assigned to
SMA
Protocol
SMA
Baudrate
9600 bd Press
to select [Baudrate] and
Bits
8
set the baud rate with
Parity
none
Stopbits
1
The SMA protocol is described in Chapter 4.8.
4.7.4 EW Protocol
At configuration of serial ports
-[Serial ports parameter] a serial port for [Asycom] has to be
selected and the protocol and communication parameters have to be set.
Setup/Serial ports
Printer
- none -
Remote display
Slot1 RS232
JBUS/MOD-Bus
none
SMA
none
Asycom
Slot1 RS485
Param
Setup/Serial ports/Slot1 RS485
Assigned to
Asycom
Protocol
Asycom V1 Select V1, V2 or V3
Baudrate
9600 bd Select e.g. [Baudrate] with
and with
Bits
8
the transfer parameter
Parity
even
Fixed setting
Stopbits
1
Fixed setting
Slave
A Select A - Z
The PR 1612 Instructions for the EW-Protocol are described in chapter 6 .