Chapter 1
Drive Configuration
the drive turning the pump at the required speed, the pressure is maintained in
the system.
However, when additional valves in the system are opened and the pressure in the
system drops, the PID error alters its output frequency to bring the process back
into control. When the PID is disabled the commanded speed is the ramped
speed reference.
When the PID is enabled, the speed reference is disconnected and PID Output
has exclusive control of the commanded speed, passing through the linear ramp
and S curve.