beautypg.com

Activating motor overload – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 171

background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

171

Diagnostics and Protection

Chapter 3

The ratio of 1:20 is the same for all durations of 150%. When operating
continuous at 100%, if the load increases to 150% for 1 second the load must
then return to 100% for 20 seconds before another step to 150%.

Activating Motor Overload

To turn on Motor Overload protection, configure P410 [Motor OL Actn]. This
activates the function. Default setting is 3 “FltCoastStop.” The following bits
configure P410 [Motor OL Actn].

“Ignore” (0) – No action is taken.

“Alarm” (1) – Type 1 alarm indicated.

“Flt Minor” (2) – Minor fault indicated. If running, drive continues to
run. Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major
fault.

“FltCoastStop” (3) – Major fault indicated. Coast to Stop.

“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.

“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

%FLA

Cold Trip Time

Hot Trip Time

105

6320

5995

110

1794

1500

115

934

667

120

619

375

125

456

240

130

357

167

135

291

122

140

244

94

145

209

94

150

180

60

155

160

50

160

142

42

165

128

36

170

115

31

175

105

27

180

96

23

185

88

21

190

82

19

195

76

17

200

70

15

IMPORTANT

If the application requires high overload current for long durations (for
example 150% for 60 seconds), heavy duty sizing (between drive and motor)
is required.

This manual is related to the following products: