beautypg.com

Sensorless vector (sv) control, Level/gains – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 50

background image

50

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 1

Drive Configuration

Sensorless Vector (SV) Control

Because the drive is not limiting the regen power the DB is able to dissipate the
power the entire decel time before duty cycle considerations limits the DB
capability.

Table 4 - Bus Regulation Curves

Level/Gains

The following parameters are Level/Gains related to bus regulation.

P374 [Bus Reg Lvl Cfg]
Bus Regulation Level Configuration - Selects the reference used to determine the
bus voltage regulation level for the bus voltage regulator and the reference used
for the dynamic brake.

“Bus Memory” (0) – References are determined based on P12 [DC Bus
Memory].

“BusReg Level” (1) – References are determined based on the voltage set in
P375 [Bus Reg Level].

If coordinated operation of the dynamic brakes of a common bus system is
desired, use this selection and set the P375 [Bus Reg Level] to coordinate the
brake operation of the common bus drives.

Voltage Class

DC Bus Memory

Bus Reg Curve 1

Bus Reg Curve 2

480

< 650V DC

Memory + 100V DC

Curve 1 - 8V DC

650V DC

≤ DC Bus Memory ≤ 685V DC

750V DC

> 685V DC

Memory + 65V DC

900

800

700

600

500

400

300

200

100

0

14

12

10

8

6

4

2

0

-0.15 0.05 0.25 0.45 0.65 0.85 1.05 1.25 1.45

DC Bus Voltage

DC Current

DC Bus

PowerFlex 750-Series Bus Regulation – Both DB First SV

Seconds

DC B

us

V

olt

s

10 V

olt

s = B

ase S
peed

Speed Fdbk

Motor Speed

Brake Current

This manual is related to the following products: