Analog outputs, Analog output specifications – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual
Page 113
Rockwell Automation Publication 750-RM002B-EN-P - September 2013
113
Feedback and I/O
Chapter 2
Analog Outputs
There are two analog outputs per I/O module. Up to five I/O modules can be
mounted in the drive ports. Se
output parameters is done by selecting the port that the module is mounted in
then accessing the Analog Output group of parameters.
Analog Output Specifications
Terminal
Name
Description
Related
Param
(4)
(4) I/O Module parameters also have a Port designation.
Sh
Shield
Terminating point for wire shields when an
EMC plate or conduit box is not installed.
Sh
Ptc–
Motor PTC (–)
Motor protection device (Positive
Temperature Coefficient).
40
on Port X
Ptc+
Motor PTC (+)
Ao0–
Analog Out 0 (–)
Bipolar, ±10V, 11 bit & sign, 2 k ohm
minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum
load.
75
on Port X
Ao0+
Analog Out 0 (+)
Ao1–
Analog Out 1 (–)
85
on Port X
Ao1+
Analog Out 1 (+)
–10V
–10 Volt Reference
2k ohm minimum.
10VC
10 Volt Common
For (–) and (+) 10 Volt references.
+10V
+10 Volt Reference
2k ohm minimum.
Ai0–
Analog Input 0 (–)
Isolated
(2)
, bipolar, differential, 11 bit &
sign.
Voltage mode: ±10V @ 88k ohm input
impedance.
Current mode: 0-20 mA @ 93 ohm input
impedance.
(2) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
50, 70
on Port X
Ai0+
Analog Input 0 (+)
Ai1–
Analog Input 1 (–)
60, 70
on Port X
Ai1+
Analog Input 1 (+)
24VC
24 Volt Common
Drive supplied logic input power.
200 mA max per I/O module
600 mA max per drive
+24V
+24 Volt DC
Di C
Digital Input Common
Common for Digital Inputs 0…5
Di 0
Digital Input 0
(1)
(1) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Be sure applied voltage is
correct for I/O module.
24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC 11.2 mA DC
115V AC, 50/60 Hz
(3)
- Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
(3) For CE compliance use shielded cable. Do not exceed 30 m (98 ft) cable length.
1
on Port X
Di 1
Di 2
Di 3
Di 4
Di 5
Sh
Sh
PTC–
PTC+
Ao0–
Ao0+
Ao1–
Ao1+
–10V
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
24VC
+24V
DiC
Di0
Di1
Di2
Di3
Di4
Di5