Test dependencies, Inertia tune – Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual
Page 37
Rockwell Automation Publication 750-RM002B-EN-P - September 2013
37
Drive Configuration
Chapter 1
Table 3 - Autotune Value Source
Inertia Tune
The Inertia Autotune selection involves only one test. Several parameters are
updated from the test results. Refer to the tables in the Individual Tests section.
A temporary command initiates an inertia test of the motor/load combination.
The motor ramps up and down while the drive measures the amount of inertia.
This option applies only to FV modes selected in P35 [Motor Ctrl Mode].
Obtain final test results with the load coupled to the motor as long as the rotation
won’t damage the machine.
Test Dependencies
When running the flux test, the selected accel rate is used unless it is less than 10
seconds. In this case, 10 seconds is forced. In the case of the Inertia test, a 0.1
second accel rate is used. The selected direction used during normal operation is
used for all rotation tests. Also, during any rotate test, the normal speed limits are
enforced.
The thermal manager is always being run in the 2 ms loop, which provides
protection during all of the Autotune tests.
Control
Mode
Motor
Type
Feedback
Select
Autotune
Rs
Xo
Idlt
Rslt
Id
Rsld
Slip
Encrls
Cemf
PmOffset
VF
Induction
NA
Static
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
Dynamic
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
PM
NA
Static
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Reluctance
NA
Static
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
FV
Induction
Encoder
Static
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
Encoderless
Static
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
OFF
PM
Encoder
Static
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
Encoderless
Static
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
Reluctance
Encoder
Static
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Encoderless
Static
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Dynamic
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF