Feedback and I/O
Chapter 2
Example
In the example below, we are using two real world inputs, such as limit switches
being wired into a PowerFlex 750-Series Option Module, and using a
DeviceLogix software program to control a digital output.
The picture below shows the DeviceLogix software Digital Input configuration.
P33 [DLX DIP 1] is configured for Port 7: Dig In Sts.Input 1 and P35 [DLX
DIP 3] is configured for Port 7: Dig In Sts.Input 3. This setup lets us bring in two
real world inputs into DeviceLogix software.
We then utilize a DeviceLogix software program so that when both Digital Input
1 and Digital Input 3 are true (on), the resultant is the DeviceLogix software
Digital Output 1 (DOP 1) turns on.
The picture below shows that the Option Module, P10 [RO0 Sel] is configured
for DeviceLogix software Port 14: DLX DigOut Sts2.DLX DOPSts1. This links
together the DeviceLogix software Digital Output 1 (DOP 1) to the drive’s
physical output, such that when the DOP 1 is high (on), the drive’s Option
Module relay output energizes.