I/o wiring – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual
Page 77
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
77
Installation and Wiring
Chapter 1
Table 31 - Drives with 690V Input - DIP Switch S15 Configuration
I/O Wiring
Observe the following points when installing I/O wiring:
•
Use copper wire only.
•
Wire with an insulation rating of 600V or greater is recommended.
Frame
Drive Current
Rating Code
S15-1
S15-2
S15-3
S15-4
S15-5
S15-6
S15-7
S15-8
C
452
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
565
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
D
678
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
791
ON
ON
OFF
OFF
OFF
OFF
ON
ON
904
ON
OFF
ON
OFF
OFF
OFF
ON
ON
1K0
OFF
ON
ON
OFF
OFF
OFF
ON
ON
1K1
ON
ON
ON
OFF
OFF
OFF
ON
ON
1K2
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
1K4
OFF
ON
OFF
ON
OFF
OFF
ON
ON
1K5
ON
ON
OFF
ON
OFF
OFF
ON
ON
IMPORTANT
I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.
ATTENTION: Configuring an analog input for current operation and driving it from
a voltage source could cause component damage. Verify proper switch
configuration prior to applying input signals. See DIP Switch and Jumper Settings
on page
ATTENTION: Hazard of personal injury or equipment damage exists when using
bipolar input sources. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.