beautypg.com

Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 164

background image

164

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

UTILIT

Y

Diagn

ost

ic

s

346

[Torque Positive]

Indicates whether the drive is operating with a positive torque reference.
1 “Active” = The drive is operating with a positive torque reference. The motor

is accelerating in the forward direction or decelerating in the negative direction
and Par 20 [Ramp Delay] has timed out.

0 “Not Active” = The drive is not operating with a positive torque reference.
Note: This parameter can be assigned to a digital output.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

20

347

[Torque Negative]

Indicates whether the drive is operating with a negative torque reference.
1 “Active” = The drive is operating with negative torque reference. The motor is

accelerating in the reverse direction or decelerating in the forward direction
and Par 20 [Ramp Delay] has timed out.

0 “Not Active” = The drive is not operating with negative torque reference.
Note: This parameter can be assigned to a digital output and is used for four
quadrant drives only.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

20

349

[CurrLimit Active]

Indicates whether or not the drive is working within the set current limits.
1 “Active” = The drive is currently in a current limited state.
0 “Not Active” =The drive is not in a current limited state.
Note: This parameter is assigned to digital output 4 (Par 148 [Digital Out4 Sel]) by
default.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

372

[Spd Limit Active]

Indicates whether the current speed reference value is limited by the defined
minimum and maximum limit values.
1 “Active” = The reference value is currently limited since the value entered is

out of range of the limit values defined.

0 “Not Active” = The reference value is within the defined limit values.
Note: This parameter can be assigned to a digital output.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A