Frame c and d fuse information – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual
Page 225
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
225
Supplemental Drive Information
Appendix A
Frame C and D Fuse Information
All fuses for armature and field circuit protection are internally mounted and
provided with frame C and D drives.
Figure 65 - Frame C and D Fuse Table Designations
Frame C and D Recommended Field Circuit Fuses
Field circuit fuses for frames C and D drives are internally mounted (labeled FU1
and FV1) and provided with the drive. See Fuse Code FS3 in
above.
Also, see
and
on page
for locations.
Table 55 - 230V AC Input Drives
Table 56 - 460V AC Input Drives
Fr
am
e
Drive
Current
Rating
Code
Field
Amps
Type
Qty Bussmann
Ferraz Shawmut (Gould
Shawmut)
SIBA
C
521
20
10 x 38 mm
2
FWC-25A10F
A60Q25-2
6003305.25
D
875
40
22 x 58 mm
FWP-50A22F
A70QS50-22F
5014006.50
1K0
Fram
e
Drive
Current
Rating
Code
Field
Amps
Type
Qty
Bussmann
Ferraz Shawmut
(Gould Shawmut)
SIBA
C
495
20
10 x 38 mm
2
FWC-25A10F
A60Q25-2
6003305.25
667
A60Q25-8
D
830
40
22 x 58 mm
FWP-50A22F
A70QS50-22F
5014006.50
996
1K1
70
FWP-100A22F
A70QS100-22F
5014006.100
1K3
1K4
U V W
C D
FS3
FS4
C1 D1
U1 V1
M
FS3 = Internally
mounted fuses for
the field circuit on
the AC input side.
FS4 = Internally
mounted fuses for
the armature
converter on the AC
input side.