beautypg.com

Reference control, Auto” speed sources, Manual” speed sources – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 280: Changing speed sources, Torque reference source, E reference control, Reference control o, For m, Figure 80

background image

280

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Appendix C

Application Notes

Reference Control

The drive speed command can be obtained from a number of different sources.
The source is determined by drive programming and the condition of the digital
inputs configured as speed selects, a digital input configured for “Auto/Manual”
or Reference Select bits of a command word (see Communication
Configurations on p
age

217

for more information).

“Auto” Speed Sources

The default auto source for a command reference (all speed select digital inputs
open or not programmed) is analog input 1 configured for “Speed Ref A”
(parameter 44 [Speed Ref A]). If any of the speed select digital inputs are closed,
the drive will use other parameters as the auto speed command source.

“Manual” Speed Sources

The manual source for speed command to the drive is either the HIM requesting
manual control (see ALT Functions on page

252

) or the control terminal block

(analog input or MOP) if a digital input is programmed to “Auto/Manual”.

Changing Speed Sources

The selection of the active speed reference can be made through the digital
inputs, DPI command, Jog button or Auto/Manual HIM operation.

Figure 80 - Speed Reference Selection Chart

Torque Reference Source

The torque reference can only be supplied by an analog input, the HIM, or a
network reference. Switching between available sources while the drive is running
is not available. Digital inputs programmed as “Speed Sel 1, 2, 3” and the HIM
Auto/Manual function (see above) do not affect the active torque reference. The
HIM, however, cannot acquire Manual Reference control while it is configured
to supply the torque reference.

Anlg In1-3 Sel
DPI P1-5 Select
MOP Select
Encoder Out Sel
Resolver Spd Sel

P44 [Speed Ref A]

P48 [Speed Ref B]

P155 [Preset Speed 2]
P156 [Preset Speed 3]
P157 [Preset Speed 4]
P158 [Preset Speed 5]
P159 [Preset Speed 6]
P160 [Preset Speed 7]

[Digital Inx Sel]

Speed Sel:

3 2 1

0 0 0

0 0 1

0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1

Auto

Auto Reference Options

Manual Reference Options
HIM (P1-P5) Requesting Manual
Anlg In1-3 Sel
MOP Select

P267 [TB Manual Ref]

Digital Input

Manual Sel

Man

Min

Speed

Limit

Off

P266 [Jog Speed]

On

P385
[Speed Ref Out]

Trim

Ramp

Ramp/
Speed

Draw

Trim

Speed/

Droop

Max

Speed

Limit

Speed

Regulator

Ref

Cmd

Jog

Cmd

Motor

Speed

Feedback

Speed

Command

Anlg In1-3 Sel
DPI P1-5 Select
MOP Select
Encoder Out Sel
Resolver Spd Sel

Anlg In1-3 Sel