Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
239
Supplemental Drive Information
Appendix A
Table 77 - 575V AC Input Drives
B
129
129
105.4
75
1321-3R160-B
56…75 (75…100)
100-D110D11
167
167
136.4
100
1321-3R160-B
56…75 (75…100)
100-D140D11
207
207
169.1
125
1321-3RB250-B
93…112 (125…150)
100-D180D11
250
250
204.3
150
1321-3RB250-B
93…112 (125…150)
100-D210ED11
330
330
269.6
200
1321-3RB320-B
149 (200)
100-D300ED11
412
412
336.6
250
1321-3RB400-B
186.4 (250)
100-D420ED11
C
495
495
404.4
300
1321-3R500-B
223.7 (300)
100-D420ED11
667
667
544.9
400
1321-3R600-B
298.3 (400)
100-D630ED11
D
830
830
678.1
500
1321-3R750-B
372.8 (500)
100-D860ED11
996
996
813.7
600
1321-3R850-B
447,4 (600)
100-D860ED11
1K1
1162
949.4
700
1321-3R1000-B
552 (700)
100-G860KD22
1K3
1328
1085.0
800
2 x1321-3R600-B
596.6 (800)
100-G860KD22
1K4
1494
1220.6
900
2 x1321-3R600-B
671.1 (900)
100-G1200KD12
Frame
Drive Current
Rating Code
DC Amps
AC Line
Amps
Hp
IP00 (Open Style)
Line Reactor Cat No.
Line Reactor kW (HP)
AC Input Contactor Cat. No.
Frame
Drive Current
Rating Code
DC Amps
AC Line Amps
Hp
IP00 (Open Style)
Line Reactor Cat No.
Line Reactor kW (HP)
AC Input Contactor Cat. No.
B
067
67.5
55.1
50
1321-3R55-B
37 (50)
100-C60D10
101
101.25
82.7
75
1321-3R100-B
56 (75)
100-C85D10
135
135
110.3
100
1321-3R130-B
75 (100)
100-D110D11
270
270
220.6
200
1321-3RB250-B
149 (200)
100-D250ED11
405
405
330.9
300
1321-3RB320-B
224 (300)
100-D420ED11
C
540
540
441.2
400
1321-3RB500-B
298 (400)
100-D630ED11
675
675
551.5
500
1321-3R600-B
373 (500)
100-D630ED11
D
810
810
661.8
600
1321-3R750-B
447 (600)
100-D860ED11
1K0
1080
882.4
800
1321-3R1000-B
597 (800)
100-G700KD22
1K2
1215
992.7
900
1321-3R1000-B
671 (900)
100-G860KD22
1K3
1350
1103.0
1000
2 x 1321-3R600-B
746 (1000)
100-G1000KD12
1K6
1687.5
1378.7
1250
2 X 1321-3R750-B
–
(1)
(1) No AC Input Contactor available for this drive rating - must be sourced locally.