Fuses for Regenerative Frame C and D Drives
Leg fuses are internally mounted and provided with frames C and D drives. See
Fuse Code FS4 in
. Also, see
on page
on page
for fuse locations.
Table 59 - Recommended Leg Fuses - 230V AC Input Frame C Drives
Table 60 - Recommended Leg Fuses - 230V AC Input Frame D Drives
Table 61 - Recommended Leg Fuses - 460V AC Input Frame C Drives
Table 62 - Recommended Leg Fuses - 460V AC Input Frame D Drives
Table 63 - Recommended Leg Fuses - 575V AC Input Frame C Drives
Table 64 - Recommended Leg Fuses - 575V AC Input Frame D Drives
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - Flush End Contact
C
521
521
426
6
170M5464 + switch 170H0069
6,9 URD 32 TTF 800 + switch MS 3-V1-5 BS
20 671 32.800 + switch 28 001 04
700
700
571
6
170M5464 + switch 170H0069
6,9 URD 32 TTF 800 + switch MS 3V 1-5 BS
20 671 32.800 + switch 28 001 04
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - DIN 43653 Stud-Mount
D
875
875
715
6
170M6263 + switch 170H0069
Y300263 + switch MS 3V 1-5 UR
20 635 32.900 + switch 28 001 04
1K0
1050
858
6
170M6264 + switch 170H0069
Z300264 + switch MS 3V 1-5 UR
20 635 32.1000 + switch 28 001 04
Fr
am
e
Drive
Current
Rating
Code
DC
Amps
AC
Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - Flush End Contact
C 495
495
404.4
6
170M5462 + switch 170H0069
6,9 URD 32 TTF 630 + switch MS 3-V1-5 BS
20 671 32.630 + switch 28 001 04
667
667
544.9
6
170M5464 + switch 170H0069
6,9 URD 32 TTF 800 + switch MS 3-V1-5 BS
20 671 32.800 + switch 28 001 04
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - DIN 43653 Stud-Mount
D
830
830
678.1
6
170M6262 + switch 170H0069
X300262 + switch MS 3V 1-5 UR
20 635 32.800 + switch 28 001 04
996
996
813.7
6
170M6264 + switch 170H0069
Z300264 + switch MS 3V 1-5 UR
20 635 32.1000 + switch 28 001 04
1K1
1162
949.4
6
170M6265 + switch 170H0069
A300262 + switch MS 3V 1-5 UR
20 635 32.1100 + switch 28 001 04
1K3
1328
1085.0
6
170M6266 + switch 170H0069
B300266 + switch MS 3V 1-5 UR
20 635 32.1250 + switch 28 001 04
1K4
1494
1220.6
6
170M6267 + switch 170H0069
C300267 + switch MS 3V 1-5 UR
20 635 32.1400 + switch 28 001 04
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC
Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - Flush End Contact
C
540
540
441
6
–
11 URD 72 TTF 0800 + switch MS 3V 1-5 BS
20 771 32.800 + switch 28 001 04
675
675
551
6
–
11 URD 72 TTF 0800 + switch MS 3V 1-5 BS
20 771 32.800 + switch 28 001 04
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - DIN 43653 Stud-Mount
D
810
810
661
6
170M6246 + switch 170H0069
J300572 + switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04
1K0
1080
881
6
170M6248 + switch 170H0069
L300574 + switch MS 3V 1-5 UR
20 735 32.1000 + switch 28 001 04
1K2
1215
991
12
170M6244 + switch 170H0069
G300570 + switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
1K3
1350
1102
12
170M6245 + switch 170H0069
H300571 + switch MS 3V 1-5 UR
20 735 32.700 + switch 28 001 04
1K6
1688
1377
12
170M6246 + switch 170H0069
J300572 + switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04