Rockwell Automation 20P PowerFlex Digital DC Drive User Manual
Page 243
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
243
Supplemental Drive Information
Appendix A
Dynamic Brake Resistor Kits
and DC Output Contactors
on page
on page
for recommended alternate
DC Output Contactors for 575V and 690V AC input drives, respectively.
Table 79 - 230V AC Input Drives
Table 80 - 460V AC Input Drives
Fram
e Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
Dynamic Brake
Resistor Kit Cat.
No.
Armature
Voltage
(Volts)
DB Resistor
Size (ohms)
DB Resistor
Size (Watts)
Brake Amps
Required
DC Loop
Contactor Cat.
No.
(3)
DC Contactor
Crimp Lugs Cat.
No.
(4)
A 7P0
7
5.7
1.5
1370-DBL62
240
20
420
12.00
1370-DC56
1370-LG40
9P0
9
7.4
2
1370-DBL63
240
20
420
12.00
1370-DC56
1370-LG40
012
12
9.8
3
1370-DBL64
240
15
420
16.00
1370-DC56
1370-LG40
020
20
16
5
1370-DBL65
240
8.6
420
27.91
1370-DC56
1370-LG40
029
29
24
7.5
1370-DBL66
240
6
345
40.00
1370-DC56
1370-LG40
038
38
31
10
1370-DBL67
240
5
330
48.00
1370-DC56
1370-LG40
055
55
45
15
1370-DBL68
240
3.5
385
68.57
1370-DC56
1370-LG56
073
73
60
20
1370-DBL69
240
2.6
385
92.31
1370-DC110
1370-LG92
093
93
76
25
1370-DBL70
240
2
330
120.00
1370-DC110
1370-LG92
110
110
90
30
1370-DBL71
240
2
330
120.00
1370-DC110
1370-LG110
B
146
146
119
40
1370-DBL72
240
0.7
280
342.86
1370-DC180
1370-LG160
180
180
147
50
1370-DBL73
240
0.5
365
480.00
1370-DC180
1370-LG180
218
218
178
60
1370-DBL74
240
0.5
365
480.00
1370-DC280
1370-LG228
265
265
217
75
1370-DBL75
240
2
330
120.00
1370-DC280
1370-LG268
360
360
294
100
1370-DBL76
240
1.4
290
171.43
(1)
(5)
434
434
355
125
(1)
240
0.5
1458
651
(1)
(5)
C
521
521
426
150
(1)
240
0.322
6221
781
(1)
(5)
700
700
572
200
(2)
240
–
–
–
(1)
(5)
D 875
875
715
250
(2)
240
–
–
–
(1)
(5)
1K0
1050
858
300
(2)
240
–
–
–
(1)
(5)
(1) See Alternate Dynamic Brake Resistor Kits and DC Output Contactors on page
.
(2) No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally.
(3) Coil voltage = 115V AC, 50/60Hz.
(4) See DC Contactor Crimp Lug Kit Specifications on page
for more information.
(5) Wire and Lug size dependant on enclosure dimensions and local codes.
Fram
e Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
Dynamic Brake
Resistor Kit Cat.
No.
Armature
Voltage
(Volts)
DB Resistor
Size (ohms)
DB Resistor
Size (Watts)
Brake Amps
Required
DC Loop
Contactor Cat.
No.
(3)
DC Contactor
Crimp Lugs Cat.
No.
(4)
A 4P1
4.1
3.3
2
1370-DBH63
500
81
255
6.17
1370-DC56
1370-LG40
6P0
6
4.9
3
1370-DBH64
500
62
245
8.06
1370-DC56
1370-LG40
010
10
8.2
5
1370-DBH65
500
45
245
11.11
1370-DC56
1370-LG40
014
14
11.4
7.5
1370-DBH66
500
27
350
18.52
1370-DC56
1370-LG40
019
19
15.5
10
1370-DBH67
500
20
420
25.00
1370-DC56
1370-LG40
027
27
22.1
15
1370-DBH68
500
12
405
41.67
1370-DC56
1370-LG40
035
35
28.6
20
1370-DBH69
500
5
330
100.00
1370-DC56
1370-LG40
045
45
36.8
25
1370-DBH70
500
4.5
330
111.11
1370-DC56
1370-LG52
052
52
42.5
30
1370-DBH71
500
3.5
385
142.86
1370-DC56
1370-LG52
073
73
59.6
40
1370-DBH72
500
2.6
345
192.31
1370-DC110
1370-LG92
086
86
70.3
50
1370-DBH73
500
2
345
250.00
1370-DC110
1370-LG92
100
100
81.7
60
1370-DBH74
500
2
345
250.00
1370-DC110
1370-LG110
129
129
105.4
75
1370-DBH75
500
1
270
500.00
1370-DC180
1370-LG140
B 167
167
136.4
100
1370-DBH76
500
0.7
280
714.29
1370-DC180
1370-LG180
207
207
169.1
125
1370-DBH77
500
0.7
280
714.29
1370-DC280
1370-LG228
250
250
204.3
150
1370-DBH78
500
0.5
365
1000.00
1370-DC280
1370-LG268
330
330
269.6
200
1370-DBH79
500
0.7
280
714.29
(1)
(5)
412
412
336.6
250
(1)
500
0.808
7292
–
(1)
(5)
C 495
495
404.4
300
(1)
500
0.595
6069
–
(1)
(5)
667
667
544.9
400
(1)
500
0.542
6439
–
(1)