Table 65 - Recommended Leg Fuses - 690V AC Input Frame C Drives
Table 66 - Recommended Leg Fuses - 690V AC Input Frame D Drives
Figure 68 - Frame C Regenerative Drive - Leg Fuse Location
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC
Line
Amps
Qty Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - Flush End Contact
C 452
452
369
6
170M5394 + switch 170H0069
12,5 URD 72 TTF 0500 + switch MS 3V 1-5 BS
20 771 32.500 + switch 28 001 04
565
565
461
6
–
12,5 URD 72 TTF 0630 + switch MS 3V 1-5 BS
20 771 32.630 + switch 28 001 04
Fram
e
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty
Bussmann
Ferraz Shawmut (Gould Shawmut)
SIBA
Square Body - DIN 43653 Stud-Mount
D
678
678
553
6
170M6244 + switch 170H0069
G300570 + switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
791
791
645
6
170M6246 + switch 170H0069
J300572 + switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04
904
904
738
6
170M6247 + switch 170H0069
K300573 + switch MS 3V 1-5 UR
20 735 32.900 + switch 28 001 04
1K0
1017
830
6
170M6248 + switch 170H0069
L300574 + switch MS 3V 1-5 UR
20 735 32.1000 + switch 28 001 04
1K1
1130
922
12
170M6244 + switch 170H0069
G300570 + switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
1K2
1243
1014
12
170M6244 + switch 170H0069
G300570 + switch MS 3V 1-5 UR
20 735 32.630 + switch 28 001 04
1K4
1413
1153
12
170M6245 + switch 170H0069
H300571 + switch MS 3V 1-5 UR
20 735 32.700 + switch 28 001 04
1K5
1582
1291
12
170M6246 + switch 170H0069
J300572 + switch MS 3V 1-5 UR
20 735 32.800 + switch 28 001 04
Note: Drive shown with front covers removed and control board EMI shield lowered.