B and the other pair for Y & Z. Figure 3 below shows how to connect the cable between the

main unit and the modules. Note how the wiring is reversed between the modules and the

main unit, but between modules the wiring is straight through.

Figure 3: Communications Bus Wiring

The modules may be located up to 2000 feet away from the main unit. Do not run AC power

lines in the same cable or conduit as the communications wiring, as this can cause data errors.

Bus Termination

Both the SCADA 3000 main unit and the final module in the chain must be terminated. A

termination jumper is located on each device. The modules (if any) branching off the main

connection are not terminated. While the main connection between the SCADA 3000 and the

most distant module can be 2000 ft., the individual modules in-between are wired on branches

called Stub lines. Stub lines can be no more than 50 ft. from the main line. (See Figure 4)

Figure 4: Communication Cable Wiring and Bus Termination