beautypg.com

Sensaphone SCADA 3000 Users manual User Manual

Page 265

background image

25-3

Chapter 25: Relay Output Module

Communications Wiring

The Relay Output Module communicates with the SCADA 3000 using a high-speed serial

communications bus. This 4-wire bus is used to connect up to 15 modules to the main unit

to provide additional inputs and/or outputs. The communications cable must be 4-Conductor

Twisted Pair. You may use unshielded cable in electrically quiet environments, but be sure to

use shielded cable if your cabling must navigate around electrical machinery or equipment.
Modules may be located a maximum of 2000' away from the main unit and should be connect-

ed in a daisy-chain fashion from one module to the next. Each module connects to the next via

a 4-wire communications cable connected to the terminals labeled A,B, Y & Z. The cable must

be 4-Conductor Twisted Pair (shielded or unshielded) with a nominal impedance of 120W

(for example, Belden #8132 or 9842 cable). Use one pair for A & B and the other pair for Y &

Z. Note how the wiring is reversed between the first module and the main unit but between

modules the wiring is straight-thru. Correct wiring setup is shown in Figure 3.

Figure 3: Correct daisy chain setup: Main unit on the end.

Figure 4: Incorrect daisy chain setup: Main unit in the middle of the chain.

The Main Unit should always be on one end of the chain, never in the middle.

Cabling Notes

Follow these guidelines to protect the communications cable from electrical interference.

• Keep the communications cable at least five feet from any electric motors, trans-

formers, rectifiers, generators, arc welders, induction furnaces, or sources of

microwave radiation.

• If you must run the cable across power lines, run them at right angles to the lines.
• Keep the communications cable at least 6 inches from AC power lines carrying

less than 20A, at least 1 foot from lines greater than 20A, and 2 feet from lines

greater than 100KVA.

• If you run the cable in a metallic wireway or conduit, keep the communications

cable at least 3 inches from AC power lines carrying less than 20A, at least 6

inches from lines greater than 20A, and 1 foot from lines greater than 100KVA.

Running the communications cable through conduit provides extra protection from physical

damage and electrical interference. If you route the cable through conduit be sure to ground