General setup, Changing the polling schedule, General setup -30 – Sensaphone SCADA 3000 Users manual User Manual

Page 112: Changing the polling schedule -30

background image

11-30

SCADA 3000 User’s Manual

poll by adding the amount of time specified in the custom time field to the time

of the previous poll.

After selecting the polling interval, choose which information you would like to download—the

Event Log and/or the Data Log. You may also choose to Reset the Data Log after download-

ing it to minimize the time of the call during the subsequent polls. Note, however, that this will

delete information in the SCADA 3000’s Data Logger, preventing another user from connect-

ing to the unit to retrieve the Data Log information. You can also print the downloaded Event

Log or Data Log by checking the appropriate boxes. When you have finished programming

the polling information, click OK.

General Setup

Next, click on the Setup tab of the Polling Schedule form. The screen shown below will

appear:

Figure 23: Polling Setup Tab

This screen contains general polling set-up parameters. The “Polling Enabled” option is, gen-

erally speaking, the polling on/off switch. If you enable it, all units in the polling schedule will

be called at their respective times. If you disable it, polling is turned off and no units will be

called. If you check “Enable polling on application startup” box, polling will be enabled every

time the SCADA 3000 software is run. If you do not check this box, polling will be disabled at

startup until you enable it manually. Checking this box is useful if you want your computer to

restart the polling process after it has rebooted for some reason such as loss of power or operat-

ing system malfunction. You may adjust the number of times the software tries to connect to

a unit if it happens to fail the first time. Enter the number in the “Retry Attempts” box. The

default setting is 3. You may also select how long to wait before retrying by entering the time

in minutes in the “Failure Delay” box. The default time is 5 minutes. When you have finished

setting these parameters, click OK.
The Results tab on the Polling Schedule form will store general polling related information

regarding polling failures, attempts, etc.

Changing the Polling Schedule

If you wish to change the polling schedule of a particular unit, simply click on the next sched-

uled poll from the Schedule tab and then click the Edit Poll button. Make your changes, then

click OK. The Polling Schedule form always shows the current polling schedule and updates its

information after each poll.