Specifications, Specifications -9 – Sensaphone SCADA 3000 Users manual User Manual
Page 253
23-9
Chapter 23: Universal Input Module
Specifications
8 Universal Inputs configurable as:
Normally Open/Normally Closed Dry Contact
Run Time (Dry Contact)
10K Thermistor
0–5V Analog Voltage (differential)
4–20mA Current Loop (differential)
10 K Thermistor Range:
-100° to 300° F (-75° to 150° C)
(+) Input Voltage VIN+:
-12V to +12V
(-) Input Voltage Vin-:
-12V to +12V
Maximum Differential Voltage (Vin+) - (Vin-):
5V
Input Resolution:
12 bits (1.22mV/count)
Typical A/D Converter Error:
±1 LSB
Input Protection:
1500 Watt transient voltage suppressor on each input
Dry Contact/Termistor Sense Voltage:
5V through 10K
4–20mA Load Resistance:
237 Ohms, 0.1%,
1
⁄
4
W
0–5V Input Impedance:
1012
Network Data Rate:
153.6 Kbps
Bus Termination Impedance:
120 Ohms
24V Output Current:
160 mA max.
Power Requirements:
10–15VDC 100mA (typical)/420mA (max.),
1.5W(typ)/6.3W(max.)
Power Fuse Rating & Type:
500mA 250V, Size TR-5 (Wickman #19372-041-K)
Operating Temperature:
32° to 158° F (0° to 70° C)
Storage Temperature:
-4° to 158° F (-20° to 70° C)
Humidity:
5 to 90% non-condensing
Dimensions:
6.1" x 6.3" x 1.2"
Weight:
0.75 lbs.
Enclosure:
Aluminum Housing with integral mounting flanges
for wall or panel installation.