Chapter 13: LCD & Keypad Programming

For individual modules 1–15, the list of diagnostics reads:

Module Type
revision
Month
Day
Year
Stack

Timeouts

There are four additional spaces at the end for future modifications to diagnostic programming

for the I/O modules.

Comm Port Baud Rate

The baud rate of each of the unit’s serial ports can be displayed from the keypad as well. To

display the baud rate, press MENU, then select Data Points and press ENTER. Press the

down arrow key until you reach Diagnostics, then press ENTER. Select Module 0 and press

ENTER, then press the down arrow key until you reach Com1 and Com2 baud rate. Press

ENTER.

Diagnosing Faults

If the fault LED is ON you can find out why by pressing MENU, then selecting DATA

POINTS by using the arrow keys. Press ENTER. Press the down arrow key until you reach

the last entry, SYSTEM FAULTS, and press ENTER. Any system faults will be displayed.

ALARmS

The second selectable item on the main menu is Alarms. Use the down arrow to move the cur-

sor to the left of Alarms, and press the ENTER keypad button.
A list appears of the 0–63 possible alarm points and the current alarm status for each. You can

scroll through the alarm list with the up and down arrow keys and press ENTER to view any

specific alarm point’s current value or to execute the Add, Remove or Freeze functions. The

first three lines of the display are: The alarm Name, the alarm UAF, and the alarm Status. An

example appears below:

Alarm 46

A, 46, 0

No alarm exists

The fourth line cycles through five choices as you press the arrow keys. The choices are: Add

to Display, Remove from Display, Acknowledge All, Acknowledge Alarm, Display Frozen.

Acknowledging Alarms from the Keypad

One or more alarms can be acknowledged at the keypad to keep the unit from dialing when

personnel are on site. The procedure below steps through the key sequence.

1) Press the MENU button, arrow-down to the Alarms category, and press

ENTER.

2) Now press the down-arrow key until you reach the alarm you want to acknowl-

edge. Press ENTER.

3) Press the down-arrow key until the LCD displays Acknowledge Alarm. Press

ENTER and the alarm will be acknowledged. If you continue to press the down-

arrow key, the Acknowledge All option will be displayed. If you press ENTER

while this message is showing, all alarms will be acknowledged.