beautypg.com

Chapter 18: system diagnostics, Main board diagnostics, Chapter 18: system diagnostics -1 – Sensaphone SCADA 3000 Users manual User Manual

Page 213: Main board diagnostics -1

background image

18-1

Chapter 18: System Diagnostics

Chapter 18: SYSTem DIAGNOSTICS

main Board Diagnostics

The SCADA 3000 includes circuitry to monitor numerous internal system parameters to

make sure that the unit is functioning properly. Some circuits are tested on power-up while

others are monitored on a continuous basis. Whenever a monitored function goes beyond its

specified limits the Fault light is lit and a description of the problem is logged in the SCADA

3000’s Event Logger. Faults can also be viewed on the LCD display. On the Keypad, select

MENU>DATA POINTS>DIAGNOSTICS>SYSTEM FAULTS. Realtime diagnostic informa-

tion can be viewed by selecting Diagnostics from the main menu and then clicking on Processors

or Motherboard. These will display system parameters monitored within the SCADA 3000 Main

Unit. The two screens shown below:

Figure 1: Processors Diagnostics

In the event of abnormal behavior, several RESET options can be performed on the unit's

microprocessors. Within the Control processor group box is a Reset button which will issue a

hardware reset to the control processor when clicked. This reset will not destroy program-

ming. At the bottom of the Processor’s Diagnostic screen are two additional reset options.

The button labeled Hardware Reset will reset both the Communications and Control proces-

sor. This type of reset will not destroy programming; however, it will drop your connection if

done while online using the modem. The Full Factory Reset will destroy all programming and

restore the unit to factory default settings (new out-of-box). Do not click this button unless you

are absolutely sure you have all programming backed up, including: SCADA 3000 unit program-

ming, Ladder program, C-Program, DataLogger downloaded, and the Event log downloaded.

Figure 2: Motherboard Diagnostics