Chapter 26: Analog Output Module
SPeCIFICATIONS
Number of Outputs:
4
Resolution:
12 bits
Max. Loop Resistance (mA type): 1000 Ohms
Output Current (sourcing):
0–20mA
Output Types:
4–20mA, 0–20mA, 0–10V
Max. Overload (output + to -):
Continuous short circuit
Power-up Status:
Output at minimum value (0mA, 4mA, or 0V)
LED Indicators:
Power LED & Pulse LED (heartbeat)
Analog Output Protection:
1500 Watt transient suppressor on each output
Network Data Rate:
153.6 Kbps
Bus Termination Impedance:
120 Ohms
Power Requirements:
10–15VDC 260mA (max.), 3.9W
Power Fuse Rating and Type:
500mA 250V, Size TR-5 (Wickmann #3720500041)
Terminal Block Wire Size:
#14AWG to #24AWG
Operating Temperature:
0° to 70° C (32° to 158° F)
Storage Temperature:
-20° to 70° C (-4° to 158° F)
Humidity:
5 to 90% non-condensing
Dimensions:
4.2" x 6.3" x 1.2"
Weight:
0.75 lbs.
Enclosure:
Aluminum Housing with integral mounting flanges
for wall or panel installation.