beautypg.com

Specifications – Sensaphone SCADA 3000 Users manual User Manual

Page 261

background image

24-7

Chapter 24: Pulse Count Module

SPeCIFICATIONS

Number of Pulse Count Inputs:

4

Compatible with dry contact switches,

relays, solid state switches and digital 5V

logic.

Input Voltage Range Vin+:

-0.5V to 5.5V DC maximum

Input Voltage Range Vin-:

-0.5V to 5.5V DC maximum

Input Sense Voltage (provided by the

module):

5VDC @ 2mA

Pulse Counting Range:

0 to 10,000 pulses per second (0–10KHz)

Input Protection:

1500 Watt transient voltage suppressor on each

input.

Network Data Rate:

153.6 Kbps

Power Requirements:

10–15VDC 100mA(max.), 1.5W

Power Fuse Rating & Type:

500mA 250V, Size TR-5

(Wickmann #3720500041)

Operating Temperature:

0° to 70° C (32° to 158° F)

Storage Temperature:

-20° to 70° C (-4° to 158° F)

Humidity:

5 to 90% non-condensing

Dimensions:

4.2" x 6.3" x 1.2"

Weight:

0.75 lbs.

Enclosure:

Aluminum housing with integral mounting

flanges for wall or panel installation.