beautypg.com

Sensaphone SCADA 3000 Users manual User Manual

Page 266

background image

25-4

SCADA 3000 User’s Manual

the entire length by connecting it to the building earth ground. For best results, use ferromag-

netic conduit near critical sources of electrical interference. You can use aluminum conduit in

non-critical areas.
Each module must be configured with its own unique address using the BUS ADDRESS

jumpers. You may mix & match up to 15 modules to suit your application’s requirements. The

example below shows a Bus Address setting of 9.

Address

Jumper Code

1

A B B B

2

B A B B

3

A A B B

4

B B A B

5

A B A B

6

B A A B

7

A A A B

8

B B B A

9

A B B A

10

B A B A

11

A A B A

12

B B A A

13

A B A A

14

B A A A

15

A A A A

Figure 5: Setting the Bus Address

Bus Termination

Located on each module is a jumper labeled BUS TERM. This jumper is used to terminate the

4-wire communications bus.

Figure 6: Bus Termination jumper

Termination is required at the extreme ends of the communications network to minimize

signal reflections that would otherwise cause data communication errors. To activate the Bus

Termination, move the jumper to the IN position. Note that this should only be activated if the

module is at the very end of the network. All other modules in between should have the ter-

mination set to the OUT position. As a result, only 1 module (plus the main unit) should ever

have the termination activated. The diagram following illustrates proper termination of the

communications bus.

Figure 7: Correct bus termination