Sensaphone SCADA 3000 Users manual User Manual
Page 280
B-2
SCADA 3000 User’s Manual
Power Supply Requirements
Input Voltage (without battery)
Input Voltage (with battery)
Current Consumption
Note: Options & I/O modules will
increase power consumption.
10–15VDC
14.7–15VDC
215mA (min)
270mA w/backlight on
add 8mA with voice option
add 85mA with modem option
add 38mA per 4–20mA loop powered from 24V supply
Aux Power Output (for I/O modules)
10–14VDC
24V Output Current
320mA max.
Battery Back-up (Optional)
12V Lead-acid Gel-cell 5.0AH to 18AH
Automatic charge control & deep discharge protection
Program memory Back-up Battery
CR2430 Lithium Battery
Power Fuse Rating and Type
4A 250V, Size TR-5 (Wickmann # 3721400041)
Terminal Block Wire Size
#14AWG to #24AWG
Operating Temperature
0 to 70 degrees Celsius (32 to 158 degrees F)
Storage Temperature
-20 to 70 degrees Celsius (-4 to 158 degrees F)
Humidity
0 to 90%, non-condensing
Dimensions
9.4" x 12.2" x 2.0"
Weight
3.0 lbs.
enclosure
Aluminum Housing with integral mounting flanges for wall or
panel installation.