5-4

SCADA 3000 User’s Manual

Figure 5: Wiring a Thermistor

Analog Voltage Output Transducers (0–5VDC)

The SCADA 3000 is compatible with transducers that produce an analog output of 0 to 5VDC.

Analog voltage output devices can be connected directly to the input terminals but be sure to

follow the polarity markings on the unit. Choose an input and connect the wires to the corre-

sponding screw terminals for that input. The configuration jumper should be set to the storage

position as indicated in the diagram below:

Figure 6: Wiring a 0-5V transducer

The shunt set to the 0–5V position is reflected in the following circuit diagram.