4-1
Chapter 4: Power Supply
Chapter 4: POWeR SUPPLY & BATTeRY
BACKUP
POWeR ReqUIRemeNTS
The SCADA 3000 is designed to be powered from a 10-15V DC power supply (15V required
to charge an external battery). This wide operating voltage range permits the unit to be pow-
ered from 12V solar cells in truly remote applications. Most applications will have 120VAC
available and we recommend using one of the 15VDC power supplies listed below:
FGD-3100 SCADA 3000 60W (15V, 4A) Hard-wired power supply
FGD-3110 SCADA 3000 50W (15V, 3.3A) Plug-in power supply with cord
Both supplies will accept inputs from 90-264 VAC 47/63Hz. The FGD-3100 has terminals for
hardwiring AC power. The FGD-3110 requires a power cord with an IEC connector on the
end (included).
The SCADA 3000 Main unit includes an Aux Power output specifically for powering SCADA
3000 expansion modules. The Aux Power terminal is backed up by the external battery.
Figure 1: Wiring from Power Supply to SCADA 3000