beautypg.com

Installation of the modem card, Chapter 4: power supply & battery, Backup – Sensaphone SCADA 3000 Users manual User Manual

Page 41: Power requirements, Installation of the modem card -5, Chapter 4: power supply & battery backup -1, Power requirements -1, Chapter 4: power supply & battery backup

background image

4-1

Chapter 4: Power Supply

Chapter 4: POWeR SUPPLY & BATTeRY
BACKUP

POWeR ReqUIRemeNTS

The SCADA 3000 is designed to be powered from a 10-15V DC power supply (15V required

to charge an external battery). This wide operating voltage range permits the unit to be pow-

ered from 12V solar cells in truly remote applications. Most applications will have 120VAC

available and we recommend using one of the 15VDC power supplies listed below:

FGD-3100 SCADA 3000 60W (15V, 4A) Hard-wired power supply
FGD-3110 SCADA 3000 50W (15V, 3.3A) Plug-in power supply with cord

Both supplies will accept inputs from 90-264 VAC 47/63Hz. The FGD-3100 has terminals for

hardwiring AC power. The FGD-3110 requires a power cord with an IEC connector on the

end (included).
The SCADA 3000 Main unit includes an Aux Power output specifically for powering SCADA

3000 expansion modules. The Aux Power terminal is backed up by the external battery.

Figure 1: Wiring from Power Supply to SCADA 3000