Mechanical installation
Standard devices in a power range from 3 ... 11 kW
Mounting in "cold plate" technique
l
75
EDS82EV903−3.0
5.3.3
Mounting in "cold plate" technique
For this mounting variant you require the controller type E82CV...
The following points are important for safe and reliable operation of the controller:
ƒ
Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at
least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all
specified screw connections.
ƒ
Observe the thermal resistance R
th
given in the table. The values are valid for
controller operation under rated conditions.
Power to be dissipated by the heatsink
Cooling path of heatsink − ambience
8200 vector
P
loss
[W]
R
th
[K/W]
E82CV302K2C
100
£ 0.23
E82CV402K2C
127
£ 0.23
E82CV552K2C
167
£ 0.13
E82CV752K2C
213
£ 0.13
E82CV302K4C
97
£ 0.23
E82CV402K4C
120
£ 0.23
E82CV552K4C
153
£ 0.23
E82CV752K4C
200
£ 0.13
E82CV113K4C
273
£ 0.13
Ambient conditions
ƒ
The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.
ƒ
Temperature at the cooling plate of the drive controller: max. 75 °C.