Commissioning
Parameter setting with the XT EMZ9371BC keypad
Vector control
l
211
EDS82EV903 EN 3.0
8.4.2
Vector control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
Comment
1.
Plug in the keypad
2.
Ensure that controller inhibit is active after mains
connection
misc001
20
28
X3
}
Terminal X3/28 = LOW
3.
Switch on the mains
ON
misc002
4.
After approx. 3 s the keypad is in the operating level
and displays the output frequency (C0050) and the
device utilisation (C0056)
9371BC004
d
A
B
b
c
0050
00
0.00 Hz
0 %
5.
For quick commissioning you select the "Quick
start" menu
9371BC006
d
A
B
b
c
p
SHPRG
Para
Code
Menu
4
3
Quick start
V e c t o r C t r l q u
The submenu "VectorCtrl qu" contains
the codes which you require for
commissioning a standard application.
The digital inputs are configured in
Lenze setting:
X3/E1, X3/E2: activation of fixed
setpoints (JOG)
X3/E3: activation of DC injection brake
(DCB)
X3/E4: CW rotation/CCW rotation
A
Change the menu level with
V
B
Change to the "Quick start" menu and there to the
"VectorCtrl qu" submenu with
z z Z z
C
Change to the code level with
Z to parameterise
your drive
Y Z
y
z
T V
S U
d
A
B
b
c
p
SHPRG
Para
Code
Menu
0034
00
0
A I N 1 r a n g e
9371BC008
6.
Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
Set the DIP switch on the standard I/O
to the same range (see Mounting
Instructions for the standard I/O)
7.
If required, adapt the fixed setpoints JOG.
A
JOG 1 (C0037)
Lenze setting: 20 Hz
Activation:
X3/E1 = HIGH, X3/E2 = LOW
B
JOG 2 (C0038)
Lenze setting: 30 Hz
Activation:
X3/E1 = LOW, X3/E2 = HIGH
C
JOG 3 (C0039)
Lenze setting: 40 Hz
Activation:
X3/E1 = HIGH, X3/E2 = HIGH
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f [ H z ]
f 2
C 0 0 1 1
f 1
0
t i r
t i f
T i r
T i f
t
T
ir
+ t
ir
@
C0011
f2 * f1
t
ir
= desired acceleration time
11.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+ t
if
@
C0011
f2 * f1
t
if
= desired deceleration time