Electrical installation, Operation at rated power – Lenze E82xVxxxKxxxxx User Manual
Page 136

Electrical installation
Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to EN 60204−1
l
136
EDS82EV903 EN 3.0
Operation at rated power
8200 vector
Rated fuse current
Cable cross−section
ELCB
1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, N, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
[mA]
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV302K2C
20
B20
4
−
³ 300
2)
³ 30
3)
E82xV402K2C
32
B25
6
4
)
−
E82xV552K2C
−
B32
6
4
)
−
E82xV752K2C
Operation only permitted with mains choke or mains filter
E82xV302K2C
16
B16
2.5
−
³ 300
2)
³ 30
3)
E82xV402K2C
20
B20
4
−
E82xV552K2C
−
B25
6
4
)
−
E82xV752K2C
−
B32
−
6
4
)
E82xV302K2C
16
B16
2.5
−
³ 300
2)
³ 30
3)
E82xV402K2C
20
B20
4
−
E82xV552K2C
−
B25
6
4
)
−
E82xV752K2C
−
B32
−
6
4
)
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV302K4C
16
B16
2.5
−
³ 300
2)
³ 30
3)
E82xV402K4C
16
B16
2.5
−
E82xV552K4C
25
B25
4
−
E82xV752K4C
32
B32
6
4)
−
E82xV113K4C
Operation only permitted with mains choke or mains filter
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV302K4C
10
B10
1.5
−
³ 300
2)
³ 30
3)
E82xV402K4C
16
B16
2.5
−
E82xV552K4C
20
B20
4
−
E82xV752K4C
20
B20
4
−
E82xV113K4C
32
B32
6
4)
−
1)
Earth−leakage circuit breaker
2)
Is used with E82EVxxxKxC0xx (with integrated EMC filter)
3)
Is used with E82EVxxxKxC2xx (without integrated EMC filter)
4)
Pin−end connector required