Dc−bus operation – Lenze E82xVxxxKxxxxx User Manual
Page 471

DC−bus operation
Fuses and cable cross−sections
DC supply
l
471
EDS82EV903−3.0
Inverter
DC fuse 14 × 51
(EFSGR0xx0AYHx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated current of fuse
Rated current of fuse
+U
G
, −U
G
Laying system
B2
C
[A]
[A]
[mm
2
]
[mm
2
]
E82xV551K4C
3/PE
400 V
12
12
1.5
1.5
E82xV751K4C
12
12
1.5
1.5
E82xV152K4C
12
12
1.5
1.5
E82xV222K4C
20
20
1.5
1.5
E82xV302K4C
20
20
2.5
2.5
E82xV402K4C
32
32
2.5
2.5
E82xV552K4C
40
40
4.0
4.0
E82xV752K4C
40
40
6.0
1)
4.0
1)
E82xV113K4C
50
50
6.0
1)
4.0
1)
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2
can be connected to the inverter.
Inverter
DC fuse NH1
(EFSGRxxx0ANVx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated current of fuse
Rated current of fuse
+U
G
, −U
G
Laying system
B2
C
[A]
[A]
[mm
2
]
[mm
2
]
E82xV153K4B
3/PE
400 V
100
100
−
25
E82xV223K4B
100
100
−
25
E82xV303K4B
200
−
−
25
E82xV453K4B
200
−
−
50
Inverter
DC fuse NH2
(EFSGRxxx0ANWx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated fuse current
Rated fuse current
+U
G
, −U
G
Laying system
F
C
[A]
[A]
[mm
2
]
[mm
2
]
E82xV553K4B
3/PE
400 V
250
−
−
95
E82xV753K4B
350
−
−
95
E82xV903K4B
350
−
95
−