Commissioning, Important codes for quick commissioning – Lenze E82xVxxxKxxxxx User Manual
Page 219

Commissioning
Important codes for quick commissioning
l
219
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0013
uSEr
Deceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change
C0011... 0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times that can be
activated via digital signals
ð
C0103
^ 286
C0014
v
Operating
mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
min
boost)
l
Commissioning is possible
without identifying motor
parameters
l
Advantage of identification
with C0148:
– Improved smooth running at
low speeds
– V/f rated frequency (C0015)
and slip (C0021) are
calculated and saved. They do
not have to be entered
^ 255
3
V/f characteristic control V ~ f
2
(square−law characteristic with
constant V
min
boost)
4
Vector control
In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50
{0.02
Hz}
960.00
l
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all
permitted mains voltages
^ 205
^ 206
C0016
uSEr
V
min
boost
а
0.00
{0.01 %}
40.00
а
device−dependent
Setting applies to all permitted
mains voltages
^ 205
C0034
*
v
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position of the
function module!
^ 298
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
2
Bipolar voltage −10 V ... +10 V
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and
gain
3
Current 4 ... 20 mA open−circuit
monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
C0034
*
v
(A)
uSEr
Range of
setpoint
selection
Application I/O
Observe jumper position of the
function module!
^ 298
1 X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output frequency
(C0010) not effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
4
Current 4 ... 20 mA open−circuit
monitored
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA