3 parameter setting with e82zbc keypad, 1 v/f characteristic control, Parameter setting with e82zbc keypad – Lenze E82xVxxxKxxxxx User Manual
Page 205: V/f characteristic control, Commissioning

Commissioning
Parameter setting with E82ZBC keypad
V/f characteristic control
l
205
EDS82EV903 EN 3.0
8.3
Parameter setting with E82ZBC keypad
8.3.1
V/f characteristic control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
Comment
1.
Connect keypad
2.
Ensure that controller inhibit is active after
mains connection
misc001
20
28
X3
}
Terminal X3/28 = LOW
3.
Switch on the mains
ON
misc002
4.
The keypad is in "Disp" mode after approx. 2 s
and indicates the output frequency (C0050)
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h PS
0050
The USEr menu is active
5.
Change to the
f mode to configure the basic
settings for your drive
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h PS
0050
z
y
w x
Blinking on the display: 0050
6.
Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h PS
0034
Set the DIP switch on the standard
I/O to the same range (see Mounting
Instructions for the standard I/O)
7.
Adapt the terminal configuration to the wiring
(C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h PS
0007
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f [ H z ]
f 2
C 0 0 1 1
f 1
0
t i r
t i f
T i r
T i f
t
T
ir
+ t
ir
@
C0011
f2 * f1
t
ir
= desired acceleration time
11.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+ t
if
@
C0011
f2 * f1
t
if
= desired deceleration time
12.
Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
0
0
C0015
V
min
V
out
f
13.
Set the V
min
boost (C0016)
Lenze setting: Depending on the controller type
The Lenze setting is suitable for all
common applications
14.
If you want to change the settings, go to the ALL
menu
For instance activate JOG
frequencies (C0037,
C0038, C0039) or motor
temperature monitoring
(C0119)