2 mains connection, Mains connection, Electrical installation – Lenze E82xVxxxKxxxxx User Manual
Page 123: Stop, Route two cables with 1.5 mm

Electrical installation
Standard devices in a power range from 0.25 ... 2.2 kW
Mains connection
l
123
EDS82EV903 EN 3.0
6.4.2
Mains connection
Controller of type E82xVxxxK2C (230/240 V mains)
(
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
^ Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
E82EV551K2C
E82EV751K2C
X1.1
X1.1
E82EV251K2C
E82EV371K2C
E82EV152K2C
E82EV222K2C
X1.1
N
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
PE
L1
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
L2
PE
L1
2/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
PE
L1
L2
L3
3/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
PE
L1
L2
2/PE AC 230 V/240 V
+UG -UG
L1
L3 PE
L2/N
PE
L1
N
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N
L3 PE
PE
L1
N
1/N/PE AC 230 V/240 V
L1
L2/N
PE
L2/N
PE
L1
L2
L3
3/PE AC 230 V/240 V
+UG -UG
L1
L3 PE
2/PE AC 230 V/240 V
PE
L1
L1
L2/N
PE
L2
0
0
8200vec012
Fig. 6−8
Mains connection 230/240 V 0.25 ... 2.2 kW
0
Route two cables with 1.5 mm
2
each to the terminals!
X1.1/+UG,
X1.1/−UG
Supply for DC−bus operation