Function library – Lenze E82xVxxxKxxxxx User Manual
Page 338

Function library
Free interconnection of analog signals
Free configuration of analog process data output words
l
338
EDS82EV903 EN 3.0
10.11.3
Free configuration of analog process data output words
Description
ƒ
The analog process data output words can be freely assigned to internal analog
process signals or monitoring signals. The controller outputs a value proportional to
the internal signal on the bus. The normalisation is indicated under C0421.
ƒ
A signal source can be assigned to several targets.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0421
*
v
Free
configuration
of analog
process data
output words
Output of analog signals to bus
^ 338
1 AIF−OUT.W1
8
Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)
Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)
2 AIF−OUT.W2
0
Output frequency
(MCTRL1−NOUT+SLIP)
3 CAN−OUT1.W1
/ FIF−OUT.W1
255
Not assigned (FIXED−FREE)
l
CAN−OUT1.W1 and
FIF−OUT.W1 are digitally
defined in the Lenze setting
and assigned to the 16 bits of
the controller status word 1
(C0417)
l
Before assigning an analog
signal source (C0421/3
¹ 255),
first delete the digital
assignment (C0417/x = 255)!
Otherwise, the output signal
would be wrong
4 CAN−OUT1.W2
/ FIF−OUT.W2
255
Not assigned (FIXED−FREE)
5 CAN−OUT1.W3
/ FIF−OUT.W3
255
Not assigned (FIXED−FREE)
6 CAN−OUT1.W4
/ FIF−OUT.W4
255
Not assigned (FIXED−FREE)
7 CAN−OUT2.W1
255
Not assigned (FIXED−FREE)
8 CAN−OUT2.W2
255
Not assigned (FIXED−FREE)
9 CAN−OUT2.W3
255
Not assigned (FIXED−FREE)
10 CAN−OUT2.W4
255
Not assigned (FIXED−FREE)