2 drive behaviour in the event of faults, Troubleshooting and fault elimination – Lenze E82xVxxxKxxxxx User Manual
Page 454

Troubleshooting and fault elimination
Drive behaviour in the event of faults
l
454
EDS82EV903 EN 3.0
11.2
Drive behaviour in the event of faults
The controller responds differently to the three possible fault types (TRIP, message, or
warning):
TRIP (keypad display:
a)
ƒ
Switches the power outputs U, V, W to high resistance until TRIP is reset.
ƒ
The fault indication is entered into C0161 of the history buffer as "current fault".
ƒ
The drive coasts without control!
ƒ
After TRIP reset (
¶ 459):
– The drive accelerates to its setpoint along the set ramps.
– The fault indication is moved to C0162 as "last fault" and is deleted in C0161.
Messages (keypad display:
c)
ƒ
Switches the power outputs U, V, W to high resistance.
ƒ
Messages are not entered into the history buffer.
ƒ
The drive coasts without control as long as the message is active!
ƒ
If the message is no longer active, the drive starts automatically.
Warnings
"Heatsink overtemperature" (keypad:OH
e)
ƒ
The drive is operated in a controlled mode!
ƒ
The warning signal goes off if the fault is no longer active.
"Error in motor phase" (keypad:LP1)
"PTC monitoring" (keypad:OH51)
ƒ
The drive is operated in a controlled mode!
ƒ
The fault indication is entered into C0161 of the history buffer as "current fault".
ƒ
After TRIP reset the fault indication is moved to C0162 as "last fault" and is deleted
in C0161.