Function library – Lenze E82xVxxxKxxxxx User Manual
Page 319

Function library
Process controller
Set control loop properties
l
319
EDS82EV903 EN 3.0
Pressure control and flow control
ƒ
The differential component K
D
(C0072) is generally not required for pressure and
flow control.
ƒ
Set the influence (C0074) to 100 %.
ƒ
Deactivate the frequency feedforward control (C0238 = 0).
Code
Setting for
Gases
Fluids
C0070 (K
P
)
0.1
0.02 ... 0.1
C0071 (T
N
)
5000 (T
N
= 5 s)
200 ... 1000 (T
N
= 0.2 s ... 1 s)
C0072 (K
D
)
0
0
Speed control
Code
Setting
C0070 (K
P
)
5
C0071 (T
N
)
100 (T
N
= 0.1 s)
C0072 (K
D
)
0
Set the influence of the process controller
ƒ
Activate frequency feedforward control (C0238 = 1). Now the process controller has
only limited influence:
– The control factor determines the influence of the process controller (C0074).
– Control factor = C0050 (output frequency) − C0051 (actual process controller value)
ƒ
C0074 refers to the maximum output frequency C0011.
ƒ
C0074 influences the stability of the control loop:
– Set C0074 as low as possible.
– If C0074 is set too high, the control loop can become unstable.
Calculate the influence of the process controller
Calculate C0074
Example
C0074 [%] + C0050 * C0051
C0011
@ 100 %
C0011 = 50 Hz, C0050 = 53 Hz, C0051 = 50 Hz:
C0074 [%] + 53 Hz * 50 Hz
50 Hz
@ 100 % + 6 %
Set the influence so that the process controller output covers the calculated value in every
working point.
Set C0074 = 10 % as guide value for the example (C0074 = 6 %). The guide value contains
tolerances which must always be observed.