8 automatic detection of motor data, Function library – Lenze E82xVxxxKxxxxx User Manual
Page 315

Function library
Automatic detection of motor data
l
315
EDS82EV903 EN 3.0
10.8
Automatic detection of motor data
Description
This function serves to determine the required motor data and influences of the motor
cable.
Must be carried out prior to initial commissioning of the vector control (C0014 = 4) or the
sensorless torque control (C0014 = 5). Otherwise commissioning will not be possible.
)
Note!
The motor data identification also influences the smooth running
performance in the "V/f characteristic control with constant V
min
boost"
operating mode (C0014 = 2 or 3). If motor data identification is carried out in
this operating mode, the smooth running performance can be optimised for
lower speeds.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0084 Motor stator
resistance
0.000 0.000
{0.001
W}
64.000
^ 315
0.0
0.0
{0.1
m
W}
6500.0 Only 8200 vector 15 ... 90 kW
C0087 Rated motor
speed
à
300
{1 rpm}
16000
à
Device−dependent
^ 315
C0088 Rated motor
current
à
0.0
0.1 (A)
650.0
à
Device−dependent
0.0 ... 2.0 x rated output current of
the controller
^ 315
C0089 Rated motor
frequency
50
10
{1 Hz}
960
^ 315
C0090 Rated motor
voltage
à
50
{1 V}
500
à
230 V for 230 V controllers,
400 V for 400 V controllers
^ 315
C0091 Motor cos
ϕ
а
0.40
{0.1}
1.0
а
Device−dependent
^ 315
C0092 Motor stator
inductance
0.0
0.000
{0.1 mH} Device−dependent
^ 315
0.00
0.00
{0.01
mH}
Device−dependent Only 8200 vector 15 ... 90 kW
C0148
*
s
Identifying
motor data
0
0
Ready
Only when the motor is cold!
1. Inhibit controller, wait until
drive is at standstill
2. Enter the correct values from
the motor nameplate in C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
v
4. Enable controller:
The identification
– starts,
c goes out
– the motor "whistles" faintly
but it does not rotate!
– takes approx. 30 s
– is completed when
c is lit
again
5. Inhibit controller
^ 315
1
Start identification
l
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
l
The motor stator resistance (C0084)
= total resistance of the motor cable