3 rated data for 500 v mains voltage, Rated data for 500 v mains voltage, Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 44

Technical data
Operation with rated power (normal operation)
Rated data for 500 V mains voltage
l
44
EDS82EV903 EN 3.0
4.4.3
Rated data for 500 V mains voltage
Basis of the data
AC mains connection
U
r
3/PE AC 400 V − 0 % ... 550 V + 0 %; 45 Hz − 0 % ... 65 Hz + 0 %
DC−mains connection
(alternatively)
U
DC
DC 565 V − 0 % ... 775 V + 0 %
Output voltage
With mains choke
V
M
3 ~ 0 ... approx. 94 % U
mains;
0 ... 650 Hz
without mains choke
V
M
3 ~ 0 ... U
mains;
0 ... 650 Hz
Periodic load change
60 s overcurrent with I
max
and 120 s base load with 75 % I
rated
Typical motor power
Three−phase asynchronous
motor (4−pole)
P
rated
[kW]
0.55
0.75
P
rated
[hp]
0.75
1.0
8200 vector type
EMC filter integrated
E82xV551K4C0xx
3)
E82xV751K4C0xx
3)
Without EMC filter
E82xV551K4C4xx
3)
E82xV751K4C2xx
3)
Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)
without mains choke
I
mains
[A]
2.0
2.6
with mains choke
I
mains
[A]
1.4
1.8
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
0.3
0.1
Rated output
current at
switching
frequency
2 kHz sin
I
r
[A]
1.4
1.9
4 kHz sin
8 kHz sin
I
r
[A]
1.4
1.9
16 kHz sin
2)
I
r
[A]
0.9
4)
1.2
4)
Max. permissible
output current for
60 s at switching
frequency
2 kHz sin
I
max
[A]
2.7
3.6
4 kHz sin
8 kHz sin
I
max
[A]
2.7
3.6
16 kHz sin
2)
I
max
[A]
1.35
4)
1.85
4)
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
50
60
E82DV... inside/outside
P
loss
[W]
17/33
20/40
E82CV... inside/cooler
P
loss
[W]
17/33
20/40
Dimensions
Dependent on the mounting variant (
^ 61)
Mass
E82EV...
m [kg]
1.2
E82DV...
m [kg]
1.2
E82CV...
m [kg]
0.9
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Switching frequency is reduced to 4 kHz if
J reaches max. − 5 °C
3)
Operation with mains voltages 484 V − 0 % ... 550 V + 0 % only permissible with brake resistor!
4)
Max. motor cable length 10 m!