Safety instructions – Lenze E82xVxxxKxxxxx User Manual
Page 26

Safety instructions
Safety instructions for the installation according to U
L
or U
R
l
26
EDS82EV903 EN 3.0
ƒ
E82xV302K2C ... E82xV752K2C (3.0 kW ... 7.5 kW, 240 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum, when protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 240 V maximum. When protected by CC, J, T or R
class fuses.
– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV302K4C ... E82xV113K4C (3.0 kW ... 11 kW, 400/500 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers (E82xV302K4C only).
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by CC, J, T or R
class fuses
– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV153K4B ... E82xV303K4B:
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV453K4B ... E82xV903K4B:
– Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.