4 technical data, 1 general data and operating conditions, Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 27: General data and operating conditions, 4technical data

Technical data
General data and operating conditions
4
l
27
EDS82EV903 EN 3.0
4
Technical data
4.1
General data and operating conditions
General data
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMC Directive
Approval
UL
cULus
Power Conversion Equipment (File No. E132659)
Protection of persons and equipment
Type of protection
EN 60529
IP20
IP41 in case of thermally separated installation
(push−through technique) between the control cabinet
(inside) and the environment.
NEMA 250
Protection against accidental contact in accordance with type
1
Earth leakage current
IEC/EN 61800−5−1
> 3.5 mA
Observe stipulations and safety
instructions!
Insulation of control
circuits
IEC/EN 61800−5−1
Safe mains isolation through double (reinforced) insulation
Insulation resistance
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Protective measures
Against short circuit, earth fault (protected against short to
earth on power−up, limited protection against short to earth
during operation), overvoltage, motor stalling, motor
overtemperature (input for PTC thermistor or thermal
contact, I
2
t monitoring)
EMC
Noise emission
IEC/EN 61800−3
Cable−guided, category C1 or C2 when using shielded motor
cables
1)
, dependent on the device variant with integrated
interference suppression or additional RFI/mains filter
0.25 ... 11 kW
E82xVxxxKxC0xx
no additional measures
E82xVxxxKxC2xx
with external filter techniques
15 ... 90 kW
E82EVxxxK4B3xx
no additional measures
E82xVxxxK4B2xx
with external filter techniques
Noise immunity
IEC/EN 61800−3
Category C2
1)