4 rating for lenze brake resistors, Rating for lenze brake resistors, Braking operation – Lenze E82xVxxxKxxxxx User Manual
Page 491

Braking operation
Braking operation with external brake resistor
Rating for Lenze brake resistors
l
491
EDS82EV903 EN 3.0
13.2.4
Rating for Lenze brake resistors
Order no.
Resistor
R
B
Continuous
power
2)
P
d
Heat
C
B
Switch−on cycle
Max. cable
cross−section
RB1, RB2
Mass
[
W]
[kW]
[kWs]
[mm
2
]
AWG
[kg]
ERBM470R020W
1)
470
0.02
3.0
3)
1:10
Brake for a
maximum of 15
s, then apply a
recovery time of
at least 135 s
4
12
0.25
ERBM470R050W
1)
470
0.05
7.5
6
10
0.60
ERBM470R100W
470
0.1
15
6
10
0.75
ERBM200R100W
1)
200
0.1
15
6
10
0.60
ERBM370R150W
370
0.15
22.5
6
10
0.95
ERBM100R150W
1)
100
0.15
22.5
6
10
0.95
ERBM082R150W
1)
82
0.15
22.5
6
10
0.95
ERBM240R200W
240
0.2
30
6
10
1.25
ERBM082R200W
1)
82
0.2
30
6
10
1.25
ERBM052R200W
1)
52
0.2
30
6
10
1.25
ERBD180R300W
180
0.3
45
10
6
2.0
ERBD100R600W
100
0.6
83
10
6
3.1
ERBD082R600W
82
0.6
87
10
6
3.1
ERBD068R800W
68
0.8
120
10
6
4.3
ERBD047R01K2
47
1.2
174
10
6
4.9
ERBD033R02K0
4)
33
2.0
240
10
6
7.1
ERBD022R03K0
4)
22
3.0
375
10
6
10.6
ERBD018R06K0
4)
18
6.0
900
10
6
10.6
ERBD018R03K0
4)
18
3.0
375
10
6
10.6
ERBD018R01K6
4)
18
1.6
240
10
6
10.6
1)
Only for controllers with a rated mains voltage of 230 V
2)
The continuous power is a reference value for the selection of brake resistors. Braking at peak braking power
(V
DC
2
/R).
3)
Braking for max. 10 s
4)
In conjunction with brake module EMB9352
)
Note!
If required, multiple brake resistors can be connected in parallel or in series:
Here, the value must not fall below the minimum permissible brake resistance
value of the controller.
13.2.5
Installation and wiring of the components for braking operation
)
Note!
Read the documentation for the accessories. Please observe the safety
instructions and operating conditions provided therein.