2 technical data, Technical data, Extensions for automation – Lenze E82xVxxxKxxxxx User Manual
Page 191

Extensions for automation
I/O function module E82ZAFSCO10 (Standard I/O PT)
Technical data
l
191
EDS82EV903 EN 3.0
7.4.2
Technical data
Operating conditions
Ambient conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 to +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 to +70 °C)
Operation
Corresponding to the data of the Lenze standard device used (see documentation
of the standard device).
Pollution
EN 61800−5−1
Degree of pollution 2
Connection data
X3/
Values
62
Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0
+60 °C)
Carrying capacity I
max
= 2 mA
8
Resolution: 10 bit
Linearity distortion: ±0.5 %
Temperature distortion: 0.3 % (0
+60 °C)
Input resistance
l
R
Input
> 50 k
W (with voltage signal)
l
R
Input
= 250
W (with current signal)
9
Carrying capacity I
max
= 10 mA
7
isolated from terminal X3/39 (GND2)
20
Load capacity:
S I
max
= 40 mA
28
Input resistance: 3.3 k
W
1 = HIGH (+12
+30 V), PLC level, HTL
0 = LOW (0
+3 V), PLC level, HTL
E1
1)
E2
1)
E3
E4
39
isolated from terminal X3/7 (GND1)
A1
Load capacity:
I
max
= 10 mA, with internal supply
I
max
= 50 mA, with external supply
1)
Frequency input alternatively 0 10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425