Display of operating data, diagnostics
Display of operating data
l
362
EDS82EV903 EN 3.0
10.15
Display of operating data, diagnostics
10.15.1
Display of operating data
Description
Important operating parameters are measured by the controller. They can be displayed
with the keypad or PC.
Some operating data can be calibrated to be displayed or selected directly with the unit of
the process quantity (e.g. pressure, temperature, speed).
)
Note!
The calibration always affects all specified codes simultaneously.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0004
*
Bar graph
display
56
1
{Code
no.}
989
l
The bar graph display shows
the selected value in % after
mains connection
l
Range −180 % ... +180 %
56 = device utilisation (C0056)
C0044
*
Setpoint 2
(NSET1-N2)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/2 =
FIXED−FREE (not assigned)
l
Display if C0412/2 is linked to
a signal source
^ 311
C0046
*
Setpoint 1
(NSET1-N1)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/1 =
FIXED−FREE (not assigned)
l
Display if C0412/1 is linked to
a signal source
^ 311
C0047
*
Torque
setpoint or
torque limit
(MCTRL1−
MSET)
400
0
{1 %}
400 The set value will be lost during
mains switching!
^ 264
Reference: Rated motor torque determined
through motor parameter identification
In "Sensorless torque control"
operating mode (C0014 = 5):
l
Torque setpoint selection if
C0412/6 = FIXED−FREE (not
assigned)
l
Torque setpoint display if
C0412/6 is linked to a signal
source
In "V/f characteristic control" or
"Vector control" operating mode
(C0014 = 2, 3, 4):
l
Display of the torque limit
value if C0412/6 is linked to a
signal source
l
Display C0047 = 400 if
C0412/6 = FIXED−FREE (not
assigned)
C0049
*
Additional
setpoint
(PCTRL1−NADD)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/3 =
FIXED−FREE (not assigned)
l
Display if C0412/3 is linked to
a signal source