3 mounting in "cold plate" technique, Mounting in "cold plate" technique, Mechanical installation – Lenze E82xVxxxKxxxxx User Manual
Page 67

Mechanical installation
Standard devices in a power range from 0.25 ... 2.2 kW
Mounting in "cold plate" technique
l
67
EDS82EV903−3.0
5.2.3
Mounting in "cold plate" technique
For this mounting variant you require the controller type E82CV...
The following points are important for safe and reliable operation of the controller:
ƒ
Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at
least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all
specified screw connections.
ƒ
Observe the thermal resistance R
th
given in the table. The values are valid for
controller operation under rated conditions.
Power to be dissipated by the heatsink
Cooling path of heatsink − ambience
8200 vector
P
loss
[W]
R
th
[K/W]
СССССС
СССССС
E82CV251K2C
СССССССССССС
СССССССССССС
20
ССССССССССССС
ССССССССССССС
£ 1.50
СССССС
СССССС
E82CV371K2C
СССССССССССС
СССССССССССС
27
ССССССССССССС
ССССССССССССС
£ 1.50
СССССС
СССССС
E82CV551K2C
СССССССССССС
СССССССССССС
33
ССССССССССССС
ССССССССССССС
£ 1.00
СССССС
E82CV751K2C
СССССССССССС
40
ССССССССССССС
£ 1.00
СССССС
СССССС
E82CV152K2C
СССССССССССС
СССССССССССС
67
ССССССССССССС
ССССССССССССС
£ 0.30
СССССС
СССССС
E82CV222K2C
1)
СССССССССССС
СССССССССССС
87
ССССССССССССС
ССССССССССССС
£ 0.30
СССССС
СССССС
E82CV551K4C
СССССССССССС
СССССССССССС
33
ССССССССССССС
ССССССССССССС
£ 1.00
СССССС
СССССС
E82CV751K4C
СССССССССССС
СССССССССССС
40
ССССССССССССС
ССССССССССССС
£ 1.00
СССССС
СССССС
E82CV152K4C
СССССССССССС
СССССССССССС
67
ССССССССССССС
ССССССССССССС
£ 0.30
СССССС
E82CV222K4C
СССССССССССС
87
ССССССССССССС
£ 0.30
1)
Max. output current at switching frequency of 8 kHz: 8.5 A!
Ambient conditions
ƒ
The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.
ƒ
Temperature at the cooling plate of the drive controller: max. 75 °C.