Page 366

Function library
Display of operating data, diagnostics
Diagnostics
l
366
EDS82EV903 EN 3.0
10.15.2
Diagnostics
Description
Display codes for diagnostics
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0093
*
Device type
xxxy
Read only
l
xxx = performance data from
the type code (e.g. 551 = 550
W)
l
y = voltage class (2 = 240 V,
4 = 400 V)
C0099
*
Software
version
x.y
Read only
x = major version, y = index
C0161
*
Active fault
Display of history buffer contents
l
Keypad: three−digit
alphanumeric fault
identification
l
Operating module 9371BB:
LECOM error number
^ 453
C0162
*
Last fault
C0163
*
Last fault but
one
C0164
*
Last fault but
two
C0168
*
Pending error
Display of history buffer "Active
fault"
l
Keypad: three−digit
alphanumeric fault
identification
l
Operating module 9371BB:
LECOM error number
^ 453
C0179
*
Power−on time
{h}
Read only
Total time of mains "ON"
C0183
*
Diagnostics
0
No fault
Read only
102
TRIP active
104
Message "Overvoltage (OU)" or
"Undervoltage (LU)" active
142
Pulse inhibit
151
Quick stop is active
161
DC injection brake active
250
Warning active
C0200
*
Software ID
Read only on PC
x = main version, y = subversion
82S8212V_xy000
8200 vector 0.25 ... 11 kW
82S8212V_xy010
8200 vector 15 ... 90 kW
C0201
*
Software
creation date
Read only on PC
C0202
*
Software ID
Output in keypad as string in four parts at four
characters each
Read only in keypad
1
82S8
2
212 V
3
_xy0
x = main version, y = subversion
4
zz
00 = 8200 vector 0.25 ... 11 kW
10 = 8200 vector 15 ... 90 kW