Parameter setting – Lenze E82xVxxxKxxxxx User Manual
Page 241

Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Transferring parameters to other standard devices
l
241
EDS82EV903 EN 3.0
Copy parameter set from the keypad to the standard device
Step
Key seq.
Action
1.
Connect the keypad to standard
device 2
2.
Inhibit controller
S
The drive coasts
3.
Select submenu 7.1, "Load/Store",
from "Param managm" in menu 7
z y Z Y
Use the arrow keys to change to the "Load/Store"
submenu
4.
Change to the code level
Z
Display C0002 "Param managm"
5.
Change to the parameter level
V
Display "0" and "READY"
6.
Select the correct copy function
The settings stored in the standard device or in the
function module are overwritten.
l
Copy all available parameter sets (PAR1 ... PAR4, if required FPAR1) into the standard device:
– Standard device with function
module application I/O,
INTERBUS, PROFIBUS−DP,
LECOM−B,
DeviceNet, CANopen
z
Copy PAR1 ... PAR4 and FPAR1:
ð Set "70" "Key−>F1&PAR1−4"
– Standard device with all other
function modules
Copy PAR1 ... PAR4:
ð Set "10" "Keypad−>PAR1−4"
l
Only copy the module−specific parameter set FPAR1 into the function module:
– Only possible with standard
devices including function
module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen:
z
Copy FPAR1:
ð Set "40" "Keypad−>FPAR1"
l
Copy individual parameter sets (PARx and FPAR1 if available) to the standard device:
– Standard device with function
module application I/O,
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
z
Copy PAR1 and FPAR1:
ð Set "71" "Key−>FP1&PAR1"
Copy PAR2 and FPAR1:
ð Set "72" "Key−>FP1&PAR2"
Copy PAR3 and FPAR1:
ðSet "73" "Key−>FP1&PAR3"
Copy PAR4 and FPAR1:
ðSet "74" "Key−>FP1&PAR4"
– Standard device with all other
function modules or standard
device without function module
Copy PAR1:
ð Set "11" "Keypad−>PAR1"
Copy PAR2:
ð Set "12" "Keypad−>PAR2"
Copy PAR3:
ð Set "13" "Keypad−>PAR3"
Copy PAR4:
ð Set "14" "Keypad−>PAR4"
7.
Start copying
T V
The selected parameter sets are copied to the
standard device or to the function module.
"LOADING..." is displayed.
When "LOADING..." goes off, the copy process is
complete.
8.
Change to the code level
A
V
Display of the operating level
B
V
Display C0002 "Param managm"
9.
Enable controller
U
The drive operates again